How to wire electric underfloor heating
Whether your electric underfloor heating can run from an existing circuit or needs its own circuit from the consumer unit depends on three things: the total load of the heating, what is already on that circuit and how the installation is built. Looking at square metres alone is not enough.
For a safe connection, the circuit, the thermostat and the heating mat must all be able to handle the load. One does not make up for another. A heavy-duty thermostat will not fix an overloaded circuit, and a generous circuit will not protect an overloaded thermostat. This guide takes you through the steps.
How is it connected?
On a standard 230 V system, the supply runs from the consumer unit to the thermostat. The thermostat switches that supply through to the heating mat or cable. For larger loads, the thermostat controls a load module or contactor that carries the heavy current instead.
The floor probe measures the temperature in the floor. That is a different job from the protective devices in the consumer unit: the probe controls the heat, the protective devices react to electrical faults and excess current.
This guide explains the choices, it is not a wiring diagram. For connecting the wires to the thermostat itself, see how to connect an electric underfloor heating thermostat. You can lay the mat yourself, but leave the final connection to a qualified electrician. In England, adding a new circuit is notifiable work under Part P of the Building Regulations, and so is most electrical work in a room with a bath or shower. A registered electrician (for example NICEIC or NAPIT) can self-certify and notify it for you. Wales and Scotland have their own building rules.
Step 1: work out the load
Use the area you will actually heat, so where the mats or cables will go. That is usually less than the full floor, because you do not heat under fitted units, the toilet or the shower tray.
Heated area × output per m² = total load in watts
Load in watts ÷ 230 volts = current in amps
| Heated area | Output per m² | Total load | Current at 230 V |
|---|---|---|---|
| 4 m² | 150 W | 600 W | 2.6 A |
| 8 m² | 150 W | 1,200 W | 5.2 A |
| 10 m² | 200 W | 2,000 W | 8.7 A |
| 15 m² | 150 W | 2,250 W | 9.8 A |
| 20 m² | 200 W | 4,000 W | 17.4 A |
This is the load the installation must supply while the heating is on. It says nothing yet about your daily usage, because the thermostat keeps switching the heating on and off. For running costs, read how many kWh electric underfloor heating uses.
Step 2: fused spur or dedicated circuit?
In UK homes there are two common routes. Smaller systems are often supplied from a fused spur: a fused connection unit with a 13 A fuse, taken from an existing ring or radial circuit. At 230 volts, 13 A works out at just under 3,000 watts, so a fused spur is only suitable for systems below that, and many electricians keep a margin. Larger areas, or a circuit that already carries heavy appliances, call for a dedicated circuit from the consumer unit.
| Connection | Typical use | Points to check |
|---|---|---|
| Fused spur (13 A fused connection unit) | Smaller areas, up to roughly 3 kW | Total load on the ring or radial it is taken from, RCD protection |
| Dedicated circuit from the consumer unit | Larger areas, or a busy existing circuit | Spare way in the consumer unit, cable size, RCBO or RCD |
| Several circuits with load modules | Very large areas on one thermostat | Each circuit fed and protected separately |
What counts is everything running at the same time. A 1,500 watt bathroom floor looks fine on a spur. But if the same circuit also feeds a 2,500 watt tumble dryer, together they draw about 17.4 amps when both are on. Never simply fit a bigger fuse or MCB because a circuit keeps tripping: it has to match the cable behind it, otherwise you remove the protection.
Step 3: choose a thermostat that can switch the load
The thermostat has a maximum too. We stock a 16 A and a 25 A version. The manufacturer's advice is slightly below the calculated value, so always follow the specification of the exact model.
| Thermostat | Switching rating | Calculated at 230 V | Manufacturer's advice |
|---|---|---|---|
| Pro-mat PS60 WiFi thermostat | 16 A | 3,680 W | approx. 3,500 W heating load |
| Pro-mat WiFi XL thermostat | 25 A | 5,750 W | up to 5,500 W heating load |
A 25 A thermostat can switch more load directly. That does not mean you can put 5,500 watts on a fused spur or an existing 16 A circuit. The circuit, cables and protection must be rated for that load.
Step 4: more power or several mats?
Several mats on one thermostat are fine, as long as the total stays within its switching rating. Two 750 watt mats add up to 1,500 watts, about 6.5 amps. Follow the manufacturer's wiring diagram and never force extra wires into a terminal that is not designed for them.
If you go over the thermostat's maximum, use a load module. The thermostat then only sends the control signal, and the module switches the heating from its own circuit. This way one thermostat can control heating on two or three 16 A circuits, for example (7,360 or 11,040 watts on paper). Each circuit is still supplied and protected separately, so two circuits do not become one bigger circuit. The load module connection diagram shows how to wire them.
Keep in mind that one thermostat is always one heating zone. All mats follow the same probe. That works well for one large room, but a probe in the bathroom tells you little about the bedroom next door. For rooms you want to control separately, use one thermostat per room.
When working on a system with load modules, isolate every circuit involved. Switching off the thermostat is not safe isolation.
Which protective devices are needed?
Each device has its own job. They are not interchangeable.
| Component | What it does | What it does not do |
|---|---|---|
| MCB or fuse | Protects against overload and short circuit | Control the floor temperature |
| RCD (30 mA) | Disconnects on earth leakage | Protect against overload |
| Earth and the mat's screen | Carries a fault safely to earth | Replace RCD or overcurrent protection |
| Thermostat with floor probe | Controls and limits the temperature | Protect the electrical installation |
Under BS 7671, the IET Wiring Regulations, electric floor heating needs additional protection by a 30 mA RCD. An RCBO combines RCD and overcurrent protection in one device, which keeps a fault on the heating from tripping other circuits. Your electrician decides which solution suits your consumer unit.
Extra points in the bathroom
In the bathroom, moisture and the bathroom zones also come into play. Not every thermostat may be fitted anywhere near the shower or bath. Before tiling, agree with your electrician where the thermostat, the supply and the floor probe will go. A waterproof heating mat does not make the wrong position for the thermostat safe.
Test and record before the floor is closed
Have the resistance and insulation of the mat tested before adhesive, levelling compound or tiles go on top. Any damage can then still be found without breaking up the floor. To check the resistance yourself, read how to measure electric underfloor heating with a multimeter. Also check that the probe works and that the thermostat is set to the correct probe setting.
Keep the readings, the electrician's certificate, the manuals and photos of the layout. They are useful if there is ever a fault, or if someone later wants to drill into the floor.
Only switch the heating on once adhesive and levelling compound have cured as specified. Never use the underfloor heating to speed up drying.
Not sure about the load?
Not sure which thermostat or how many load modules you need? Get in touch with us and we will be happy to help.